Application
GMC (LS) series AC contactor is suitable for using in the circuits up to the rated voltage 660VAC 50Hz or 60Hz, rated current 9A to 135A, making and breaking and frequent starting, controls the AC motor. Combined with the auxiliary contact group, air delayer, machine interlocking device etc, it is combined into the delay contactor, mechanical interlocking contactor, drat-delta starter, with the thermal relay, it is combined into the electro magnetic starter. This product conforms to the requirement of IEC 60947 -1 & GB14048.4 standards.
Specification
Product name | Factory price three phase gmc-32 240v ac contactor | ||||||||
Type | GMC-9 | GMC-12 | GMC-18 | GMC-22 | GMC-32 | GMC-40 | |||
IEC-60947 | AC1 duty | 20A | 20A | 25A | 32A | 50A | 60A | ||
AC-3 duty | 220-240V | 2.5KW 11A | 3.5KW 13A | 4.5KW 18A | 5.5KW 22A | 7.5KW 32A | 11KW 40A | ||
380-440V | 4KW 9A | 5.5KW 12A | 7.5KW 18A | 11KW 22A | 15KW 32A | 18.5KW 40A | |||
500-550V | 4KW 7A | 7.5KW 12A | 7.5KW 13A | 15KW 22A | 18.5KW 32A | 22KW 32A | |||
690V | 4KW 5A | 7.5KW 9A | 7.5KW 9A | 15KW 18A | 18.5KW 21A | 22KW 25A | |||
UL | Continuous current(th) | 20A | 25A | 30A | 32A | 45A | 50A | ||
AC Motor | Single Phase | 115V | 0.5HP | 0.5HP | 1HP | 2HP | 2HP | 3HP | |
230V | 1HP | 2HP | 3HP | 3HP | 5HP | 5HP | |||
Three Phase | 200V | 2HP | 3HP | 5HP | 7HP | 7.5HP | 10HP | ||
230V | 2HP | 3HP | 5HP | 7.5HP | 10HP | 10HP | |||
460V | 5HP | 7.5HP | 10HP | 10HP | 20HP | 25HP | |||
575V | 7.5HP | 10HP | 15HP | 15HP | 20HP | 25HP | |||
Aux. Contact | Side mounting | AU-1 | AU-1 | AU-1 | AU-1 | AU-1 | AU-1 | AU-1 | |
Top mounting | AU-2,AU-4 | AU-2,AU-4 | AU-2,AU-4 | AU-2,AU-4 | AU-2,AU-4 | AU-2,AU-4 | AU-2,AU-4 | ||
Panel installation | Rail & Screw | ||||||||
External Dimension(mm)(W*H*D) | 44x80x86.8 | 68x82x94.6 | |||||||
NORMALAUNNING AND INSTALLATION CONDITIONS
•Ambient air temperature:-5℃~+40℃, the average value should not exceed+35℃ within 24 hours.
•Elevation:at most 2000m.
•Atmospheric conditions:When the temperature at 40, the relative humidity of atomsphere should be at the most 50%. When at relatively low temperatures, it could have higher relative humidity. Monthly maximum relative humidity could be not more than 90% . Special measures should be taken due to occurrence of dews.
•Class of pollution:Class 3
•Installation category: III
•Installation conditions:Degree of inclination between fitting surface and vertical surface should not exceed I
•Impact shock:Product should be installed and used in the place where often shakes and impacts.